Utilising the proven and trusted FG Wilson generator set design, the 8.5 – 290 kVA range provides power that is uncompromising on quality with the introduction of FG Wilson engines and a simplified choice of options. The FG Wilson engines provide reliable power suitable for nonregulated markets or non-mobile applications. Combined with the Marelli alternator, providing coastal insulation protection and a RFI filter as standard, a trusted performance is guaranteed.

GENERATOR SET SPECIFICATIONS

Minimum Rating 250.0 kVA / 200.0 kW
Maximum Rating 275.0 kVA / 220.0 kW
Voltage 220-415 Volts
Frequency 50 Hz
Speed 1500 RPM
50 Hz Prime Rating 250.0 kVA / 200.0 kW
50 Hz Standby Rating 275.0 kVA / 220.0 kW
60 Hz Prime Rating - / -
60 Hz Standby Rating - / -

GENERATOR SET CONFIGURATIONS

Emissions/Fuel Strategy Fuel Optimised

ENGINE SPECIFICATIONS

Engine Model FG Wilson FD6-10.3A1
Compression Ratio 16.8:1
Governor Type Electronic
Bore 123.0 mm (4.8 in)
Displacement 10.3l (630.9 cu .in.)
Stroke 145.0 mm (5.7 in)

Features

FG WILSON DIESEL ENGINE

MARELLI ALTERNATOR

DCP-10 CONTROL PANEL

The FG Wilson DCP range allows you to monitor and control your generator set with ease, providing important diagnostic information whilst ensuring your unit operates within safe parameters. FG Wilson DCP digital control panels, provide simple, intuitive menu navigation and control of your generator set operations. Key information is displayed via the LCD screen and LED’s using universally recognised symbols, eliminating the need for complex instructions or language settings.

DESIGN CRITERIA

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

SINGLE-SOURCE SUPPLIER

Fully prototype tested with certified torsional vibration analysis available

WORLD WIDE PRODUCT SUPPORT

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

*Technical specifications may vary for some products, Please send us an enquiry to receive the updated information.

Our Location

  • Laurus Technologies LLCAl Emadi Business Centre
    Office No. 27, First Floor
    C Ring road
    Doha, Qatar
  • Call Us+974 447 82465

Have A Query?